GENERAL SPECIFICATIONS
• Low input current total harmonic distortion (THD)
• Galvanic isolation at output
• High input power factor
• High efficiency up to 93,5%
• Cold start function
• Static and maintenance by-pass switch
• Output short circuit and overload protection
• External REPO switch input
• 512 events memory (512 events 45000 alarms)
• Clock and calender (battery supported)
• Automatic battery test,remaining battery time indicator
• Temperature compansated charge system (optional) (opsiyonel)
• 2 RS232 serial ports and 12 dry contact outputs
• 3 DSP controlled modular structure
• Optional graphical panel
• Optional usb flash memory
• Optional SNMP and MODBUS adaptors
• Manufactured according to EC Directive; EN62040
• Full digital structure
• Small footprint
• Ecomode operation (optional)
• Fewer electronic components
• Output current limiting
• Advanced diagnostics for the input
• Selectable input/output voltage/frequency/range
• Split by-pass input (second input)
• Output DC leakage protection
• Separate DSP for inverter control
• Separate DSP for the PFC
• 3 level battery protection
• High charge current capacity
• Charge/discharge current indicator
• Advanced remote control
• 2 years warranty
TECHNICIAL SPECIFICATIONS
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 10 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 9 |
Power factor | 0,9 |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 336 VDC (2X28 batteries) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 280 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1 , EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 57 dBA |
Weight (kg) | 187 |
Dimension (mm) HxWxD | 400x815x1040 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 15 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 13,5 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 57 dBA |
Weight (kg) | 198,5 |
Dimension (mm) HxWxD | 400x815x1040 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 20 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 18 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 62 dBA |
Weight (kg) | 244 |
Dimension (mm) HxWxD | 400x815x1040 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 30 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 27 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 62 dBA |
Weight (kg) | 270 |
Dimension (mm) HxWxD | 400x815x1040 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 40 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 36 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 62 dBA |
Weight (kg) | 393 |
Dimension (mm) HxWxD | 515x855x1440 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 60 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 54 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 64 dBA |
Weight (kg) | 457 |
Dimension (mm) HxWxD | 515x855x1440 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 80 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 72 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 64 dBA |
Weight (kg) | 536 |
Dimension (mm) HxWxD | 515x855x1440 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 100 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 90 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 68 dBA |
Weight (kg) | 539 |
Dimension (mm) HxWxD | 825x855x1770 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 120 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 108 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 68 dBA |
Weight (kg) | 595 |
Dimension (mm) HxWxD | 825x855x1770 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 160 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 144 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 68 dBA |
Weight (kg) | 647 |
Dimension (mm) HxWxD | 825x855x1770 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 200 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 180 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 68 dBA |
Weight (kg) | 910,5 |
Dimension (mm) HxWxD | 825x855x1770 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 250 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 225 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | 72 dBA |
Weight (kg) | 1150 |
Dimension (mm) HxWxD | 1250x1055x1900 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 300 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 270 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | 72 dBA |
Weight (kg) | 1283 |
Dimension (mm) HxWxD | 1250x1055x1900 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 400 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 360 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | ± 312 VDC (2x26 batts) |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 351 VDC / ± 260 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
INDICATORS | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | 72 dBA |
Weight (kg) | 1497 |
Dimension (mm) HxWxD | 1250x1055x1900 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | Up to 8 units |
(*) | Depending on power and input/output conditions |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 500 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± 10% |
Power factor (at100% load) | ≥ 0.99 |
THDI (*) | ≤ %3 |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
OUTPUT | |
Power (kW) | 400 |
Power factor | 0.8 |
Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | up to 94% |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | ≤ 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | 2x28 batteries |
Float charging voltage | ± 378 VDC |
Float / End of dischg voltage | ± 280 VDC |
Battery Housing | External |
Battery ambient temp | 25ºC |
Protections | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
Indicators | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
Inputs | EPO input, Interactive battery panel input, Genset input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Software (3 clients + 1 server management) |
Alarm Logging | Standard: with time & date 512 events |
Protections | Power module over-temperature, Over current, Temperature high alarm |
Temperature Range | 0ºC - 40ºC |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | 72 dBA |
Weight (kg) | 2402 |
Dimension (mm) HxWxD | 2020x2250x770 |
OPTIONS | |
Input / Output voltage | Please ask |
Transformer | Galvanic isolation transformer at input (optional) |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), TCP/IP, GSM/GPRS Modem, Comport multiplexer |
Parralel Operation | up to 8 units |
(*) | Depending on power and input/output conditions |