GENERAL SPECIFICATIONS
• True double-conversion
• Microprocessor control optimizes reliability
• Input power factor correction
• Output power factor 0.9
• Wide input voltage
• Converter mode available
• Generator compatible
• ECO mode for energy saving (Only available for 1-3kVA models)
• Adjustable charging current via LCD or soſtware (1A~6A)
• Emergency power off (EPO) function is only available for 6/10kVA models
• Comprehensive display allows easy monitoring and access to UPS status
TECHNICIAL SPECIFICATIONS
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 1000 VA / 900 W |
INPUT | |
Nominal Voltage | 110/115/120/127VAC or 208/220/230/240VAC |
Input voltage range | 60-145 VAC or 120-300 VAC at 50% load 90-145 VAC or 180-300 VAC at 100% load |
Frequency range | 40Hz ~ 70 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Output voltage | 110/115/120/127VAC or 208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 47~ 53 Hz or 57 ~ 63 Hz |
Frequency range (batt. mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz |
Output current crest factor | 3:1 |
THD | ≤ 3 % THD (Linear Load), ≤ 6 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | 4 ms (Typical) |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %88 |
Battery Mode | %83 |
BATTERY | |
Battery type | 12V / 9AH |
Numbers | 2 |
Typical recharge time | 4 hours recover to 90% capacity |
Charging current (max.) | 1.0A |
Float charging voltage | 27.4VDC ± %1 |
INDICATORS | |
LCD display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 438x310x88 |
Weight (kg) | 12 |
ENVIRONMENT | |
Relative humidity | 20-90 % RH @ 0- 40°C (non-condensing) |
Noise level | < 55dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 2000 VA / 1800 W |
INPUT | |
Nominal Voltage | 110/115/120/127VAC or 208/220/230/240VAC |
Input voltage range | 60-145 VAC or 120-300 VAC at 50% load 90-145 VAC or 180-300 VAC at 100% load |
Frequency range | 40Hz ~ 70 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Output voltage | 110/115/120/127VAC or 208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 47~ 53 Hz or 57 ~ 63 Hz |
Frequency range (batt. mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz |
Output current crest factor | 3:1 |
THD | ≤ 3 % THD (Linear Load), ≤ 6 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | 4 ms (Typical) |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %89 |
Battery Mode | %87 |
BATTERY | |
Battery type | 12V / 9AH |
Numbers | 4 |
Typical recharge time | 4 hours recover to 90% capacity |
Charging current (max.) | 1.0A |
Float charging voltage | 54.7VDC ± %1 |
INDICATORS | |
LCD display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 438x410x88 |
Weight (kg) | 19 |
ENVIRONMENT | |
Relative humidity | 20-90 % RH @ 0- 40°C (non-condensing) |
Noise level | < 55dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 3000 VA / 2700 W |
INPUT | |
Nominal Voltage | 110/115/120/127VAC or 208/220/230/240VAC |
Input voltage range | 60-145 VAC or 120-300 VAC at 50% load 90-145 VAC or 180-300 VAC at 100% load |
Frequency range | 40Hz ~ 70 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Output voltage | 110/115/120/127VAC or 208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 47~ 53 Hz or 57 ~ 63 Hz |
Frequency range (batt. mode) | 50 Hz ± 0.25 Hz veya 60Hz ± 0.3 Hz |
Output current crest factor | 3:1 |
THD | ≤ 3 % THD (Linear Load), ≤ 6 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | 4 ms (Typical) |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %90 |
Battery Mode | %88 |
BATTERY | |
Battery type | 12V / 9AH |
Numbers | 6 |
Typical recharge time | 4 hours recover to 90% capacity |
Charging current (max.) | 1.0A |
Float charging voltage | 82.1VDC ± %1 |
INDICATORS | |
LCD display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 438x630x88 |
Weight (kg) | 29.3 |
ENVIRONMENT | |
Relative humidity | 20-90 % RH @ 0- 40°C (non-condensing) |
Noise level | < 55dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 6000 VA / 5400 W |
INPUT | |
Input voltage range | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) |
Frequency range | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Output voltage | 208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz |
Frequency range (batt. mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Output current crest factor | 3:1 |
THD | ≤ 3 % THD (Linear Load), ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | 0ms |
Transfer time | Inverter -> bypass | 0ms |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %92 |
Battery Mode | %90 |
BATTERY | |
Battery type | 12V / 9AH |
Numbers | 16 - 20 |
Typical recharge time | 9 hours recover to 90% capacity |
Charging current (max.) | 1A/2A (Adjustable) |
Float charging voltage | 218.4VDC ± %1 - 273VDC ± %1 |
INDICATORS | |
LCD display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | KGK: 438x530x88 [2U] - Battery Pack: 438x668x88 [2U] KGK: 438x530x88 [2U] - Battery Pack: 438x580x133 [3U] |
Weight (kg) | KGK: 15 - Battery Pack:48 KGK: 15 Battery Pack:61 |
ENVIRONMENT | |
Relative humidity | 0-95 % RH @ 0- 40°C (non-condensing) |
Noise level | < 55dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 10000 VA / 9000 W |
INPUT | |
Input voltage range | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) |
Frequency range | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Output voltage | 208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz |
Frequency range (batt. mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Output current crest factor | 3:1 |
THD | ≤ 3 % THD (Linear Load), ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | 0ms |
Transfer time | Inverter -> bypass | 0ms |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %93 |
Battery Mode | %91 |
BATTERY | |
Battery type | 12V / 9AH |
Numbers | 16 - 20 |
Typical recharge time | 9 hours recover to 90% capacity |
Charging current (max.) | 1A/2A (Adjustable) |
Float charging voltage | 218.4 VDC ± %1 - 273VDC ± %1 |
INDICATORS | |
LCD display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | KGK: 438x580x133[3U] -Battery Pack: 438x580x133 [3U] KGK: 438x580x133[3U] - Battery Pack: 438x580x133 [3U] |
Weight (kg) | KGK: 18 - Battery Pack:51 KGK: 18 Battery Pack:61 |
ENVIRONMENT | |
Relative humidity | 0-95 % RH @ 0- 40°C (non-condensing) |
Noise level | < 55dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |