GENERAL SPECIFICATIONS
• True double-conversion
• Microprocessor control optimizes reliability
• Input power factor correction
• Wide input voltage
• Converter mode available
• ECO mode for energy saving (Only available for 1-3kVA models)
• Generator compatible
• Adjustable battery numbers only available for 6/10kVA models
• Adjustable charging current via LCD or soſtware (1A~ 6A) only available for 6/10kVA models
• Emergency power off (EPO) function is only available for 6/10kVA models
• Comprehensive display allows easy monitoring and access to UPS status
TECHNICIAL SPECIFICATIONS
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 1000VA / 800W |
INPUT | |
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Input voltage range | 60-150 VAC or 120-300 VAC (Based on load at 50%) 90-140 VAC or 180-280 VAC (Based on load at 100%) |
Frequency range | 40Hz ~ 70 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Power factor | 0,8 |
Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 47~ 53 Hz or 57 ~ 63 Hz |
Frequency range (batt. mode) | 50 Hz or 60Hz ± %0.5 |
Output current crest factor | 3:1 (maks) |
THD | ≤ 3% THD (linear load) ≤ 6% THD (non-linear load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | 4 ms |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %88 |
Battery Mode | %83 |
BATTERY | |
Battery type | Depending on the applications |
Numbers | 2 |
Typical recharge time | 4 hour recover to 90% capacity |
Charging current (max.) | 1A/2A/4A/6A (adjustable) |
Float charging voltage | 27.4VDC ± %1 - 41.9VDC ± %1 |
INDICATORS | |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 145x282x220 |
Weight (kg) | 4.1 |
ENVIRONMENT | |
Relative humidity | 20-90% RH @ 0- 40°C (non-condensing |
Noise level | < 50dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 2000VA / 1600W |
INPUT | |
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Input voltage range | 60-150 VAC or 120-300 VAC (Based on load at 50%) 90-140 VAC or 180-280 VAC (Based on load at 100%) |
Frequency range | 40Hz ~ 70 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Power factor | 0,8 |
Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 47~ 53 Hz or 57 ~ 63 Hz |
Frequency range (batt. mode) | 50 Hz or 60Hz ± %0.5 |
Output current crest factor | 3:1 (maks) |
THD | ≤ 3% THD (linear load) ≤ 6% THD (non-linear load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | 4 ms |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %89 |
Battery Mode | %85 |
BATTERY | |
Battery type | Depending on the applications |
Numbers | 4 |
Typical recharge time | 4 hour recover to 90% capacity |
Charging current (max.) | 1A/2A/4A/6A (adjustable) |
Float charging voltage | 54.7 VDC ± %1 - 82.1VDC ± %1 - 109.4 VDC ± %1 |
INDICATORS | |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 145x397x220 |
Weight (kg) | 6.8 |
ENVIRONMENT | |
Relative humidity | 20-90% RH @ 0- 40°C (non-condensing |
Noise level | < 50dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 3000VA / 2400W |
INPUT | |
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
Input voltage range | 60-150 VAC or 120-300 VAC (Based on load at 50%) 90-140 VAC or 180-280 VAC (Based on load at 100%) |
Frequency range | 40Hz ~ 70 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Power factor | 0,8 |
Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 47~ 53 Hz or 57 ~ 63 Hz |
Frequency range (batt. mode) | 50 Hz or 60Hz ± %0.5 |
Output current crest factor | 3:1 (maks) |
THD | ≤ 3% THD (linear load) ≤ 6% THD (non-linear load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | 4 ms |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %90 |
Battery Mode | %88 |
BATTERY | |
Battery type | Depending on the applications |
Numbers | 6 |
Typical recharge time | 4 hour recover to 90% capacity |
Charging current (max.) | 1A/2A/4A/6A (adjustable) |
Float charging voltage | 82.1 VDC ± %1 - 109.4 VDC ± %1 |
INDICATORS | |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 145x397x220 |
Weight (kg) | 7.4 |
ENVIRONMENT | |
Relative humidity | 20-90% RH @ 0- 40°C (non-condensing |
Noise level | < 50dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 6000VA / 5400W |
INPUT | |
Nominal Voltage | 208/220/230/240VAC |
Input voltage range | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) |
Frequency range | 46~54 Hz or 56~64 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Power factor | 0,9 |
Voltage | 208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 46~54 Hz or 56~64 Hz |
Frequency range (batt. mode) | 50 Hz or 60Hz ± %0.5 |
Output current crest factor | 3:1 (maks) |
THD | ≤ 3% THD (linear load) ≤ 6% THD (non-linear load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %92 |
Battery Mode | %90 |
BATTERY | |
Battery type | Depending on the applications |
Numbers | 16-20 (adjustable) |
Typical recharge time | 9 hour recover to 90% capacity |
Charging current (max.) | 1A/2A/4A/6A (adjustable, only for 6A 16 pcs batt. configuration) |
Float charging voltage | 273 VDC ± 1% (according to 20 batt.-powered configuration) |
INDICATORS | |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 190x369x318 |
Weight (kg) | 12 |
ENVIRONMENT | |
Relative humidity | 0-95% RH @ 0-40°C (non-condensing) |
Noise level | < 50dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
TECHNICIAL SPECIFICATIONS | |
Phase | Single phase with ground |
Capacity | 10000VA / 9000W |
INPUT | |
Nominal Voltage | 208/220/230/240VAC |
Input voltage range | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) |
Frequency range | 46~54 Hz or 56~64 Hz |
Power factor | ≥ 0.99 @ Nominal Voltage (100% load) |
OUTPUT | |
Power factor | 0,9 |
Voltage | 208/220/230/240VAC |
GVoltage tolerance | ± %1 |
Frequency range | 46~54 Hz or 56~64 Hz |
Frequency range (batt. mode) | 50 Hz or 60Hz ± %0.5 |
Output current crest factor | 3:1 (maks) |
THD | ≤ 3% THD (linear load) ≤ 6% THD (non-linear load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
EFFICIENCY | |
AC Mode | %93 |
Battery Mode | %91 |
BATTERY | |
Battery type | Depending on the applications |
Numbers | 16-20 (adjustable) |
Typical recharge time | 9 hour recover to 90% capacity |
Charging current (max.) | 1A/2A/4A/6A (adjustable, only for 6A 16 pcs batt. configuration) |
Float charging voltage | 273 VDC ± 1% (according to 20 batt.-powered configuration) |
INDICATORS | |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
ALARM | |
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continously sounding |
PHYSICAL | |
Dimension (mm) HxWxD | 190x442x318 |
Weight (kg) | 16 |
ENVIRONMENT | |
Relative humidity | 0-95% RH @ 0-40°C (non-condensing) |
Noise level | < 50dBA @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |