The new Tescom DS Power SH UPS appears as a cost effective and smaller footprint UPS. Using the 3 level inverter topology and control system, this series UPS have the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. Efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.
GENERAL SPECIFICATIONS
• Transformerless UPS topology
• Low input current total harmonic distortion (THD)
• High input power factor
• High efficiency up to 94%
• Cold start function
• Static and maintenance by-pass switch
• Output short circuit and overload protection
• 3 Level topology
• 192 events memory (192 events 14.400 alarms)
• Clock and calender (battery supported)
• Automatic battery test ,remaining battery time indicator
• Temperature compensated charge system (optional)
• 1 RS232 serial port and 3 dry contact outputs (+2 optional)
• 3 DSP controlled modular structure
• Optional SNMP and MODBUS adaptors
• Manufactured according to EC Directive; EN62040
• Full digital structure
• Small footprint
• Fewer electronic components
• Output current limiting
• Advanced diagnostics for the input
• Selectable input/output voltage/frequency/range
• Output DC leakage protection
• Separate DSP for PFC 3 level battery protection
• Charge/discharge current indicator
• Advanced remote control
• Manufactured under CE,ISO9001,ISO14001,TSE and GOST international standards
• 2 years warranty
TECHNICIAL SPECIFICATIONS
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 10 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± %10 |
Power factor (at100% load) | ≥ 0.99 |
THDI (at 100% load) | ≤ 4% (depends on mains input conditions) |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency Tolerance |
OUTPUT | |
Power (kW) | 9 |
Power factor | 0,9 (1 optional) |
Voltage | 380/400 VAC 3P + N , ± 1% (415 VAC optional) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | %94 |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | < 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | 2x30 (±30): 60 pieces |
Float charging voltage | ± 405 VDC |
Float / End of dischg voltage | ± 300 VDC |
Battery Housing | External |
Battery ambient temp | 25°C |
Protections | |
Battery ambient temp | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 satır LCD panel, Mimik led panel, 5 vektör butonlar, buzer |
Indicators | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | RS232 serial port, 4 standard DRY contact alarm relays |
Inputs | EPO input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0°C - 40°C |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 55 dBA |
Weight (kg) | 47.5 |
Dimension (mm) HxWxD | 700x300x770 (without batt.) / 1000x300x800 (with 5ah batt.) /1170x300x800 (with 7-9ah batt.) |
OPTIONS | |
Input / Output voltage | Please ask |
Comm. adaptors | SNMP, MODBUS, RS485, Remote panel |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 15 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± %10 |
Power factor (at100% load) | ≥ 0.99 |
THDI (at 100% load) | ≤ 4% (depends on mains input conditions) |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency Tolerance |
OUTPUT | |
Power (kW) | 13,5 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N , ± 1% (415 VAC optional) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | %94 |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | < 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | 2x30 (±30): 60 pieces |
Float charging voltage | ± 405 VDC |
Float / End of dischg voltage | ± 300 VDC |
Battery Housing | External |
Battery ambient temp | 25°C |
Protections | |
Battery ambient temp | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 satır LCD panel, Mimik led panel, 5 vektör butonlar, buzer |
Indicators | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | RS232 serial port, 4 standard DRY contact alarm relays |
Inputs | EPO input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0°C - 40°C |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 57 dBA |
Weight (kg) | 49.5 |
Dimension (mm) HxWxD | 700x300x770 (without batt.) / 1000x300x800 (with 5ah batt.) /1170x300x800 (with 7-9ah batt.) |
OPTIONS | |
Input / Output voltage | Please ask |
Comm. adaptors | SNMP, MODBUS, RS485, Remote panel |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
TECHNICIAL SPECIFICATIONS | |
Nominal power (kVA) | 20 |
INPUT | |
Voltage | 380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional) |
Frequency | 50Hz / 60Hz, ± %10 |
Power factor (at100% load) | ≥ 0.99 |
THDI (at 100% load) | ≤ 4% (depends on mains input conditions) |
By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
Protection | Fuses, Voltage & Frequency Tolerance |
OUTPUT | |
Power (kW) | 18 |
Power factor | 0,9 (0,8 and 1 optional) |
Voltage | 380/400 VAC 3P + N , ± 1% (415 VAC optional) |
Frequency | 50Hz / 60Hz |
Frequency Tolerance | Line synchronized: ± 2% (adjustable) / Free running: ± 0,1% |
Efficiency (at 100% load) | %94 |
Output current crest factor | 3:1 |
Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
THD | < 2% (at 100% linear load) |
BATTERIES | |
Type | VRLA AGM / GEL / NiCd |
Battery Number | 2x30 (±30): 60 pieces |
Float charging voltage | ± 405 VDC |
Float / End of dischg voltage | ± 300 VDC |
Battery Housing | External |
Battery ambient temp | 25°C |
Protections | |
Battery ambient temp | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
Automatic Testing | Standard every 72 hours (adjustable) |
GENEL | |
Standards | EN62040-1, EN62040-2, EN62040-3 |
User Interface | 4 satır LCD panel, Mimik led panel, 5 vektör butonlar, buzer |
Indicators | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
Communication | RS232 serial port, 4 standard DRY contact alarm relays |
Inputs | EPO input |
Genset Kit | Standard (programmable) |
Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
Alarm Logging | Standard:with time & date 512 events |
Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
Temperature Range | 0°C - 40°C |
Protection class | IP20 |
Relative humidity | 90% max. (non-condensing) |
Altitude | < 1000m above sea level |
Noise level | < 57 dBA |
Weight (kg) | 51 |
Dimension (mm) HxWxD | 700x300x770 (without batt.) / 1000x300x800 (with 5ah batt.) /1170x300x800 (with 7-9ah batt.) |
OPTIONS | |
Input / Output voltage | Please ask |
Comm. adaptors | SNMP, MODBUS, RS485, Remote panel |
Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |