GENERAL SPECIFICATIONS
• DSP technology guarantees high performance
• Output power factor 1.0
• Active power factor correction in all phases
• Dual Inputs
• 50Hz/60Hz frequency converter mode
• ECO mode operation for energy saving
• Emergency power off function (EPO)
• Adjustable charging current
• Very powerful charger
• Optional parallel operation with common battery
• High overload capability
• Adjustable battery design
• Optional 4.3”touch LCD
TECHNICIAL SPECIFICATIONS
TECHNICIAL SPECIFICATIONS | |
Phase | 3 phase in / 3 phase out |
Capacity | 10kVA / 10kW |
Parallel capability | 3 |
INPUT | |
Nominal Voltage | 3 x 400VAC (3F+N) |
Nominal Voltage | Input voltage range | 190-520VAC (3-Phase) @ 50% load 305-478VAC (3-Phase) @ 100% load |
Frequency range | 46~54Hz or 56~64Hz |
Power factor | ≥ 0.99 @ 100% load |
OUTPUT | |
Output voltage | 3 x 360*/380/400/415 VAC (3F+N) |
AC Voltage regulation | ± %1 |
Frequency range | 46~54Hz or 56~64Hz |
Frequency range (batt. mode) | 50Hz ± 0.1Hz or 60Hz ± 0.1Hz |
Output current crest factor | 3:1 (max.) |
THD | ≤ 2 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
Overload | Battery Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
EFFICIENCY | |
AC Mode | %95.5 |
Eco Mode | %98.5 |
Battery Mode | %94.5 |
BATTERY | |
Battery type | 12V 9Ah |
Numbers | 20 pcs |
Charging current (max.) | 2-12A adjustable |
Float charging voltage | ± 136.5 VDC ±%10 |
INDICATORS | |
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
PHYSICAL | |
Uzun süreli model | Dimension (mm) HxWxD | 250x630x826 |
Uzun süreli model | Weight (kg) | 124 (with internal battery) |
ENVIRONMENT | |
Operating temperature | 0-40°C |
Relative humidity | < 95% and non-condersing |
Noise level | < 60dB @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
NOT | |
(*) | As the output voltage is 3 x 360VAC, the output power of the unit will be reduced to 90% |
TECHNICIAL SPECIFICATIONS | |
Phase | 3 phase in / 3 phase out |
Capacity | 20kVA / 20kW |
Parallel capability | 3 |
INPUT | |
Nominal Voltage | 3 x 400VAC (3F+N) |
Nominal Voltage | Input voltage range | 190-520VAC (3-Phase) @ 50% load 305-478VAC (3-Phase) @ 100% load |
Frequency range | 46~54Hz or 56~64Hz |
Power factor | ≥ 0.99 @ 100% load |
OUTPUT | |
Output voltage | 3 x 360*/380/400/415 VAC (3F+N) |
AC Voltage regulation | ± %1 |
Frequency range | 46~54Hz or 56~64Hz |
Frequency range (batt. mode) | 50Hz ± 0.1Hz or 60Hz ± 0.1Hz |
Output current crest factor | 3:1 (max.) |
THD | ≤ 2 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
Overload | Battery Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
EFFICIENCY | |
AC Mode | %95.5 |
Eco Mode | %98.5 |
Battery Mode | %94.5 |
BATTERY | |
Battery type | 12V 9Ah |
Numbers | 32 pcs (can be extended with external cabinet) |
Charging current (max.) | 2-12A adjustable |
Float charging voltage | ± 218 VDC ± %10 |
INDICATORS | |
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
PHYSICAL | |
Uzun süreli model | Dimension (mm) HxWxD | 250x630x826 |
Uzun süreli model | Weight (kg) | 139 (with internal battery) |
ENVIRONMENT | |
Operating temperature | 0-40°C |
Relative humidity | < 95% and non-condersing |
Noise level | < 63dB @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
NOT | |
(*) | As the output voltage is 3 x 360VAC, the output power of the unit will be reduced to 90% |
TECHNICIAL SPECIFICATIONS | |
Phase | 3 phase in / 3 phase out |
Capacity | 30kVA / 30kW |
Parallel capability | 3 |
INPUT | |
Nominal Voltage | 3 x 400VAC (3F+N) |
Nominal Voltage | Input voltage range | 190-520VAC (3-Phase) @ 50% load 305-478VAC (3-Phase) @ 100% load |
Frequency range | 46~54Hz or 56~64Hz |
Power factor | ≥ 0.99 @ 100% load |
OUTPUT | |
Output voltage | 3 x 360*/380/400/415 VAC (3F+N) |
AC Voltage regulation | ± %1 |
Frequency range | 46~54Hz or 56~64Hz |
Frequency range (batt. mode) | 50Hz ± 0.1Hz or 60Hz ± 0.1Hz |
Output current crest factor | 3:1 (max.) |
THD | ≤ 2 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
Overload | Battery Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
EFFICIENCY | |
AC Mode | %95.5 |
Eco Mode | %98.5 |
Battery Mode | %94.5 |
BATTERY | |
Battery type | Depends on the application |
Numbers | 32~40 pcs (Adjustable) |
Charging current (max.) | 2-12A adjustable |
Float charging voltage | ±13,65 VxN (N = 16~20) |
INDICATORS | |
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
PHYSICAL | |
Uzun süreli model | Dimension (mm) HxWxD | 300x815x1000 |
Uzun süreli model | Weight (kg) | 60 |
ENVIRONMENT | |
Operating temperature | 0-40°C |
Relative humidity | < 95% and non-condersing |
Noise level | < 65dB @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
NOT | |
(*) | As the output voltage is 3 x 360VAC, the output power of the unit will be reduced to 90%. |
TECHNICIAL SPECIFICATIONS | |
Phase | 3 phase in / 3 phase out |
Capacity | 40kVA / 40kW |
Parallel capability | 3 |
INPUT | |
Nominal Voltage | 3 x 400VAC (3F+N) |
Nominal Voltage | Input voltage range | 190-520VAC (3-Phase) @ 50% load 305-478VAC (3-Phase) @ 100% load |
Frequency range | 46~54Hz or 56~64Hz |
Power factor | ≥ 0.99 @ 100% load |
OUTPUT | |
Output voltage | 3 x 360*/380/400/415 VAC (3F+N) |
AC Voltage regulation | ± %1 |
Frequency range | 46~54Hz or 56~64Hz |
Frequency range (batt. mode) | 50Hz ± 0.1Hz or 60Hz ± 0.1Hz |
Output current crest factor | 3:1 (max.) |
THD | ≤ 2 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
Overload | Battery Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
EFFICIENCY | |
AC Mode | %95.5 |
Eco Mode | %98.5 |
Battery Mode | %94.5 |
BATTERY | |
Battery type | Depends on the application |
Numbers | 32~40 pcs (Adjustable) |
Charging current (max.) | 2-12A adjustable |
Float charging voltage | ±13,65 VxN (N = 16~20) |
INDICATORS | |
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
PHYSICAL | |
Uzun süreli model | Dimension (mm) HxWxD | 300x815x1000 |
Uzun süreli model | Weight (kg) | 61 |
ENVIRONMENT | |
Operating temperature | 0-40°C |
Relative humidity | < 95% and non-condersing |
Noise level | < 70dB @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
NOT | |
(*) | As the output voltage is 3 x 360VAC, the output power of the unit will be reduced to 90%. |
TECHNICIAL SPECIFICATIONS | |
Phase | 3 phase in / 3 phase out |
Capacity | 60kVA / 60kW |
Parallel capability | 3 |
INPUT | |
Nominal Voltage | 3 x 400VAC (3F+N) |
Nominal Voltage | Input voltage range | 190-520VAC (3-Faz) @ %50 yük 305-478VAC (3-Faz) @ %100 yük |
Frequency range | 46~54Hz or 56~64Hz |
Power factor | ≥ 0.99 @ 100% load |
OUTPUT | |
Output voltage | 3 x 360*/380/400/415 VAC (3F+N) |
AC Voltage regulation | ± %1 |
Frequency range | 46~54Hz or 56~64Hz |
Frequency range (batt. mode) | 50Hz ± 0.1Hz or 60Hz ± 0.1Hz |
Output current crest factor | 3:1 (max.) |
THD | ≤ 2 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
Overload | Battery Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
EFFICIENCY | |
AC Mode | %95.5 |
Eco Mode | %98.5 |
Battery Mode | %94.5 |
BATTERY | |
Battery type | Depends on the application |
Numbers | 32~40 pcs (Adjustable) |
Charging current (max.) | 2-24A adjustable |
Float charging voltage | ±13,65 VxN (N = 16~20) |
INDICATORS | |
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
PHYSICAL | |
Uzun süreli model | Dimension (mm) HxWxD | 360x790x1010 |
Uzun süreli model | Weight (kg) | 108 |
ENVIRONMENT | |
Operating temperature | 0-40°C |
Relative humidity | < 95% and non-condersing |
Noise level | < 70dB @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
NOT | |
(*) | As the output voltage is 3 x 360VAC, the output power of the unit will be reduced to 90%. |
TECHNICIAL SPECIFICATIONS | |
Phase | 3 phase in / 3 phase out |
Capacity | 80kVA / 80kW |
Parallel capability | 3 |
INPUT | |
Nominal Voltage | 3 x 400VAC (3F+N) |
Nominal Voltage | Input voltage range | 190-520VAC (3-Faz) @ %50 yük 305-478VAC (3-Faz) @ %100 yük |
Frequency range | 46~54Hz or 56~64Hz |
Power factor | ≥ 0.99 @ 100% load |
OUTPUT | |
Output voltage | 3 x 360*/380/400/415 VAC (3F+N) |
AC Voltage regulation | ± %1 |
Frequency range | 46~54Hz or 56~64Hz |
Frequency range (batt. mode) | 50Hz ± 0.1Hz or 60Hz ± 0.1Hz |
Output current crest factor | 3:1 (max.) |
THD | ≤ 2 % THD (Linear Load) ≤ 5 % THD (Non-linear Load) |
Transfer time | AC Mode -> Battery Mode | Zero |
Transfer time | Inverter -> bypass | Zero |
Waveform (batt. mode) | Pure Sinewave |
Overload | AC Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
Overload | Battery Mode | 100-110% for 60 min, 110-125% for 10 min, >150% immediately |
EFFICIENCY | |
AC Mode | %95.5 |
Eco Mode | %98.5 |
Battery Mode | %94.5 |
BATTERY | |
Battery type | Depends on the application |
Numbers | 32~40 pcs (Adjustable) |
Charging current (max.) | 2-24A adjustable |
Float charging voltage | ±13,65 VxN (N = 16~20) |
INDICATORS | |
LCD panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
PHYSICAL | |
Uzun süreli model | Dimension (mm) HxWxD | 360x790x1010 |
Uzun süreli model | Weight (kg) | 113 |
ENVIRONMENT | |
Operating temperature | 0-40°C |
Relative humidity | < 95% and non-condersing |
Noise level | < 75dB @ 1 meter |
Managament | |
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
NOT | |
(*) | As the output voltage is 3 x 360VAC, the output power of the unit will be reduced to 90%. |